Technical data
-
Working temperature:
Min. 5 °C/Max. 80 °C (90 °C briefly)
Art.no. 066399, 066418: Min. 5 °C/Max. 70 °C (80 °C briefly)
-
Ambient temperature:
Min. 1 °C/Max. 60 °C
-
Max. working pressure:
1.0 MPa (10 bar)
-
Max. differential pressure:
100 kPa (1 bar)
-
Leakage:
< 0.1% of Kvs at 100 kPa
-
Angle of rotation:
60°/360°
-
Media 1:
Water - Glycol mixture max. 50% Ethanol mixture max. 30%
-
Thread standard:
Rp - female thread, G - male thread, ISO 228/1
-
Actuator:
7 VA, 230 VAC, 50 Hz
7 VA, 24 VAC, 50 Hz
-
Operation time:
8 seconds (60°)
-
Electrical connection:
Fixed wire alternatively Molex®-compatible connector
-
Signal connector:
Single pole SPST
-
Protection class:
IP 40 (Molex®) / IP 44 (Cable)
-
Material, valve body:
Brass EN 12165 CW617N
-
Material, external cover:
Brass EN 12164 CW614N
-
Material, slide/spindle:
PPS Composite
-
Cable specification:
Dimension 3 x 0.75 mm²
-
Wire colors:
Blue, brown, black
-
External insulation:
PVC
-
Connection:
Molex® or Molex®-compatible connector, 6-circuit
-
Approvals:
LK 525 MultiZone 3W is a motorized 3-way zone valve for On/Off control. The zone valve is designed with a turning slide which allows it to withstand a larger pressure difference and reduces the risk of it stalling after a long intermission. This makes it especially suited for heat pump applications where there can be long intermissions between the changes to the direction of the flow during the warm season. On the upper surface of the actuator is an indicator that shows which port is open.
The zone valve must not be installed with the motor underneath the valve unit.
In case of a power failure, the valve cone stays in its current position.
When the power is switched off, the valve can be manually set to the centre position, which distributes the flow between the heating and tap water circuits. Remove the motor and turn the spindle about 30° or turn until hot water flows through both valve ports. When the power is restored, turn the valve back to its original position and reinstall the motor.
Please note that the motor can be installed in only one position.