Technical data
-
Working temperature:
Min. 5 °C/Max. 80 °C
(90 °C briefly)
-
Ambient temperature:
Min. 1 °C/Max. 60 °C
-
Max. working pressure:
1.0 MPa (10 bar)
-
Max. differential pressure:
100 kPa (1 bar)
-
Leakage:
< 0.1% of Kvs at 100 kPa
-
Angle of rotation:
90°/360°
-
Media 1:
Water - Glycol mixture max. 50% Ethanol mixture max. 30%
-
Thread standard:
Rp - female thread, G - male thread, ISO 228/1
-
Actuator:
7 VA, 230 VAC, 50 Hz
-
Operation time:
12 seconds (90°)
-
Electrical connection:
Fixed wire
-
Signal connector:
Single pole SPST
-
Protection class:
IP 44
-
Material, valve body:
Brass EN 12165 CW617N
-
Material, external cover:
Brass EN 12164 CW614N
-
Material, slide/spindle:
PPS Composite
-
Cable specification:
Dimension 3 x 0,75 mm²
-
Wire colors:
Blue, brown, black
-
External insulation:
PVC
-
Approvals:
LK 525 MultiZone is a motorized 2-way zone valve for application in heating systems in which the flow through one or more zones is to be controlled. The zone valve has On/Off control and is designed with a turning slide which allows it to withstand a larger pressure difference and reduces the risk of it stalling after a long intermission. On the upper surface of the actuator is an indicator that shows which port is open or closed.
The zone valve must not be installed with the motor underneath the valve unit.
In case of a power failure, the valve cone stays in its current position. When the power is switched off, the valve can be manually set. Remove the motor and turn the spindle to your selected position. When the power is restored, turn the valve back to its original position and reinstall the motor.
Please note that the motor can be installed in only one position.